15 Commissioning
Installation and operation manual
18
FXFN-B
CO₂ VRV system air conditioner
3P672850-2C – 2024.11
NOTICE
Be sure to keep the power line and interconnection line
apart from each other. Interconnection wiring and power
supply wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block (symbols P1, P2) and fix
the cable with a tie wrap.
3 Interconnection cable: Route the cable through the frame,
connect the cable to the terminal block (make sure the symbols
F1, F2 match with the symbols on the outdoor unit), and fix the
cable with a tie wrap.
4 Power supply cable: Route the cable through the frame and
connect the cable to the terminal block (L, N, earth).
a
b
a Circuit breaker
b Residual current device
5 Divide the small sealing (accessory) and wrap it around the
cables to prevent water from entering the unit.
6 Seal all gaps with a sealing material (field supply) to prevent
small animals from entering the system.
7 Reattach the service cover.
a
(mm)
e
b
c
10~15
70~90
10~20
d
c
b
e
10~15
d
70~90
7
N L
a Service cover (with wiring diagram)
b Opening for cables
c Connection of power supply
d Tie wrap
e Connection of user interface and interconnection cable
Complete system example
▪ Example: 1 user interface controls 1 indoor unit.
IN/D OUT/D
F
1 F2 F1 F2
Control box
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
L N L N L N L N
a
d
c
b
NL NL NL NL
a Outdoor unit
b Indoor unit
c User interface
d Most downstream indoor unit
▪ Example: Group control or use with 2 user interfaces.
IN/D OUT/D
F
1 F2 F1 F2
Control box
P
1
P
2
F
1
P
1
P
2
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
P
1
P
2
N
N
L
L
NL L N L N
b
c
e
d
a
a Outdoor unit
b Indoor unit
c User interface (controls 3 indoor units)
d Most downstream indoor unit
e For use with 2 user interfaces
▪ Setting master unit (Cooling/Heating masterhood). In case of
group control, connect the user interface wiring directly to the
master unit. Do not connect user interfaces directly to slave units.
Slave units are restricted in their operation by the master unit (e.g.
1 outdoor unit does not allow for 1 indoor unit to run in cooling
operation while another runs in heating operation). For setting
using the user interface, refer to the manual or reference guide of
the user interface.
▪ 2 or more user interfaces: When using 2 or more user
interfaces, one must be
set to "MAIN" and the other to "SUB". For setting procedure see
the installation
and operation manual of the used user interface.
INFORMATION
In case of group control, it is not necessary to assign a
group address to the indoor unit. The group address is
automatically set when the power is turned on.
15 Commissioning
NOTICE
General commissioning checklist. Next to the
commissioning instructions in this chapter, a general
commissioning checklist is also available on the Daikin
Business Portal (authentication required).
The general commissioning checklist is complementary to
the instructions in this chapter and can be used as a
guideline and reporting template during commissioning and
hand-over to the user.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.
15.1 Checklist before commissioning
1 After the installation of the unit, check the items listed below.
2 Close the unit.
3 Power up the unit.
You have read the complete installation and operation
instructions described in the installer and user reference
guide.