11 About the box
Installation and operation manual
12
FXFN-B
CO VRV system air conditioner
3P672850-2C – 2024.11
For the installer
11 About the box
11.1 Indoor unit
11.1.1 To remove the accessories from the
indoor unit
a e fdcb
h i
g
j
p
on
k l
m
a Paper pattern for installation (top part of packing box)
b General safety precautions
c Indoor unit installation and operation manual
d Installation guide
e Washers for hanger brackets
f Screws (to temporarily attach the paper pattern for
installation to the indoor unit)
g Tie wraps
h Metal clamp
i Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
j Drain hose
k Power supply cable
l Communication cable
m Addendum for auto cleaning panel installation manual
n Insulation piece: Small (liquid pipe)
o Insulation piece: Large (gas pipe)
p Insulation piece (drain pipe)
12 Unit installation
NOTICE
Make sure to install all necessary countermeasures in case
of refrigerant leakage according to standard EN378.
12.1 Preparing the installation site
12.1.1 Installation site requirements of the
indoor unit
CAUTION
This equipment is NOT intended for use in residential
locations and will NOT guarantee to provide adequate
protection to radio reception in such locations.
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
NOTICE
The professional installer shall evaluate the EMC
situation before installation, if the equipment is installed
closer than 30m to a residential location.
Special installation measures are NOT required to
minimize EMC (electro-magnetic) emissions.
NOTICE
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
INFORMATION
Equipment meets the requirement for commercial and
light-industrial location when professionally installed and
maintained.
CAUTION
Excessive concentrations of refrigerant R744 (CO
2
) in a
closed room can lead to unconsciousness and oxygen
deficiency. Take appropriate measures.
Spacing. Mind the following requirements:
(mm)
≥1500
2000
4000
≥1500
A
B
C
ba dac
A Minimum distance to the wall (see below)
B Minimum and maximum distance to the floor (see below)
C 40~63 class:
≥269mm: In case of installation with standard decoration
panel
≥311mm: In case of installation with design decoration
panel
≥349mm: In case of installation with auto cleaning
decoration panel
≥319mm: In case of installation with standard panel +
fresh air intake kit
≥361mm: In case of installation with design panel + fresh
air intake kit
80 class: