Daikin FXDA15A2VEB handleiding

28 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 12 van 28
7 Maintenance and service
Installation and operation manual
12
FXDA10~63A2VEB
VRV system air conditioner
3P599562-1C – 2022.02
3 Dry the air filter in the shadow.
4 Reattach the air filter. Hook the filter behind the flap and
attach the filter to the main unit while pushing down on the
hooks.
rear suction
2
1
bottom suction
2
1
5 Make sure that hooks are properly fixed.
6 Turn ON the power.
7 To remove warning screens, see the reference guide of the
user interface.
7.2.2 To clean the air outlet
WARNING
Do NOT let the indoor unit get wet. Possible
consequence: Electrical shock or fire.
Clean with a soft cloth. If it is difficult to remove stains, use water or
a neutral detergent.
7.3 Maintenance before a long stop
period
E.g., at the end of the season.
Let the indoor units run in fan only operation for about half a day in
order to dry the interior of the units.
Clean air filters and casings of indoor units (see "7.2Cleaning the
air filter and air outlet"[411]).
Remove the batteries from the user interface (if applicable).
7.4 Maintenance after a long stop
period
E.g., at the beginning of the season.
Check and remove everything that might be blocking inlet and
outlet vents of indoor units and outdoor units.
Clean the air filter and the casing of the indoor unit (see
"7.2Cleaning the air filter and air outlet"[411]).
Insert batteries in the user interface (if applicable).
7.5 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
Periodical inspections for refrigerant leaks may be required
depending on the applicable legislation. Contact your installer for
more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does NOT leak. If the refrigerant leaks in the
room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the
formation of a harmful gas.
Turn OFF any combustible heating devices, ventilate
the room, and contact the dealer where you purchased
the unit.
Do NOT use the unit until a service person confirms
that the part from which the refrigerant leaked has been
repaired.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
Be aware that the refrigerant inside the system is
odourless.
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Contact your installer for more information.
7.5.1 About the refrigerant leakage sensor
WARNING
The R32 refrigerant leakage sensor must be replaced after
every detection or at the end of its lifetime. ONLY
authorised persons may replace the sensor.
NOTICE
Functionality of the safety measures are periodically
automatically checked. In case of malfunction, an error
code will be displayed on the user interface.
NOTICE
The R32 refrigerant leakage sensor is a semiconductor
detector which may incorrectly detect substances other
than R32 refrigerant. Avoid using chemical substances
(e.g. organic solvents, hair spray, paint) in high
concentrations, in the close proximity of the indoor unit
because this may cause misdetection of the R32
refrigerant leakage sensor.

Bekijk gratis de handleiding van Daikin FXDA15A2VEB, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelFXDA15A2VEB
CategorieAirco
TaalNederlands
Grootte4251 MB