12 Unit installation
Installation and operation manual
18
FXAA15~63AUV1B
VRV system air conditioner
3P622285-1C – 2022.02
12.3.3 To remove the pipe port cover
INFORMATION
To connect the piping on right-side, right-bottom, left-side
or left-bottom, the pipe port cover MUST be removed.
a
b
a Cut off for side piping
b Cut off for bottom piping
1 Remove the front grille.
2 Cut off the pipe port cover from inside the front grille using a
coping saw.
3 Remove any burrs along the cut section using a half round
needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.
12.3.4 To hook the unit on the mounting plate
1 Remove the front panel.
2 Set the indoor unit on the mounting plate hooks. Use the " "
marks as a guide.
3 Place piece of packing material for support.
a
c
db e
a Front grille
b Refrigerant piping
c Tab 2×
d Mounting plate (accessory)
e Piece of packing material
12.3.5 To pass the pipes through the wall hole
1 Connect the drain piping "12.3.6 To provide drainage" [4 18],
the refrigerant piping "13 Piping installation" [4 20] and the
electrical wiring "14Electrical installation"[420].
2 Shape the refrigerant pipes along the pipe path marking on the
mounting plate.
3 Fix the electrical wiring and the refrigerant pipes together using
vinyl tape (field supply).
c
e f
b
d
a
A
A
c g
a Drain hose
b Wall hole
c Refrigerant piping
d Electrical wiring
e Vinyl tape (field supply)
f Power supply wiring
g Transmission wiring and user interface wiring
NOTICE
▪ Do NOT bend refrigerant pipes.
▪ Do NOT push the refrigerant pipes onto the bottom
frame or the front grille.
4 Pass the drain hose and refrigerant piping through the wall hole
and seal the gap with a putty.
5 When the complete installation is finished (drain piping
"12.3.6 To provide drainage" [4 18], the refrigerant piping
"13 Piping installation" [4 20] and the electrical wiring
"14 Electrical installation" [4 20]), fix the indoor unit on the
mounting plate "15.1 To fix the unit on the mounting
plate"[422].
12.3.6 To provide drainage
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Pipe length. Keep drain piping as short as possible.