38 English
Specifi cation of Power Supply Wire and Air Switch
Outdoor Unit:
Model
Power Supply
(V, Ph, Hz)
Capability of Air
Switch
Minimum Sectional
Area of Earth Wire
Minimum Sectional
Area of Power
Supply Wire
(A) (mm²) (mm²)
RY24PEV1K
R24PEV1K
220-240, 1, 50 25 4.0 4.0
RY30PEV1K
R30PEV1K
220-240, 1, 50 25 4.0 4.0
RY36PEY1K
R36PEY1K
380-415, 3, 50 20 4.0 4.0
RY42PEY1K
R42PEY1K
380-415, 3, 50 25 4.0 4.0
RY48PEY1K
R48PEY1K
380-415, 3, 50 25 4.0 4.0
Indoor Unit:Duct Type
Model
Power Supply
(V, Ph, Hz)
Capability of Air
Switch
Minimum Sectional
Area of Earth Wire
Minimum Sectional
Area of Power
Supply Wire
(A) (mm²) (mm²)
FDYM24PEV1K
FDM24PEV1K
220-240, 1, 50 6 1.0 1.0
FDYM30PEV1K
FDM30PEV1K
220-240, 1, 50 6 1.0 1.0
FDYM36PEV1K
FDM36PEV1K
220-240, 1, 50 10 1.5 1.5
FDYM42PEV1K
FDM42PEV1K
220-240, 1, 50 10 1.5 1.5
FDYM48PEV1K
FDM48PEV1K
220-240, 1, 50 10 1.5 1.5
01_EN_EM09A058A.indd 3801_EN_EM09A058A.indd 38 5/13/2010 11:43:40 AM5/13/2010 11:43:40 AM