5.5.7 Low Discharge Superheat fault
This alarm indicates that the unit has worked for too long with low discharge super heat.
Symptom
Cause
Solution
Circuit status is Off.
The circuit is switched off with the
shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 OffDishSHLo
String in the alarm log:
CxCmp1 OffDishSHLo
String in the alarm snapshot
CxCmp1 OffDishSHLo
EEXV is not working correctly.
It’s not opening enough or it’s moving
in the opposite direction.
Check if pump-down can be finished
for pressure limit reached;
Check expansion valve movements.
Check connection to the valve driver
on the wiring diagram.
Measure the resistance of each
winding, it has to be different from 0
Ohm.
Reset
Notes
Local HMI
Network
Auto
x 2 attempts (W/C only)
5.5.8 Oil Pressure Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Solution
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 OffOilFeedPSen
String in the alarm log:
CxCmp1 OffOilFeedPSen
String in the alarm snapshot
CxCmp1 OffOilFeedPSen
Sensor is broken.
Check for sensor integrity.
Check correct sensors operation
according information about mVolt
(mV) range related to pressure values
in kPa.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected
(open).
Check for correct installation of the
sensor on refrigerant circuit pipe. The
transducer must be able to sense the
pressure through the valve’s needle.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
Reset
Notes
Local HMI
Network
Auto
5.5.9 Suction Temperature Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Solution
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 OffSuctTempSen
String in the alarm log:
CxCmp1 OffSuctTempSen
String in the alarm snapshot
CxCmp1 OffSuctTempSen
Sensor is shorted.
Check for sensor integrity.
Check correct sensors operation according
information about kOhm (k) range related to
temperature values.
Sensor is broken.
Check if sensor is shorted with a resistance
measurement.
Sensor is not good
connected (open).
Check for correct installation of the sensor on
refrigerant circuit pipe.
Check for absence of water or humidity on sensor
electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with
electrical scheme.
Reset
Notes
Local HMI
Network
Auto