5.4 Circuit Alerts
5.4.1 Economizer Pressure Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Solution
Circuit status is On.
Economizer is Off.
Bell icon is moving on controller’s
display.
String in the alarm list:
Cx EcoPressSen
String in the alarm log:
Cx EcoPressSen
String in the alarm snapshot
Cx EcoPressSen
Sensor is broken.
Check for sensor integrity.
Check correct sensors operation
according information about mVolt
(mV) range related to pressure values
in kPa.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected
(open).
Check for correct installation of the
sensor on refrigerant circuit pipe. The
transducer must be able to sense the
pressure through the valve’s needle.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
Reset
Notes
Local HMI
Network
Auto
5.4.2 Economizer Temperature Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Solution
Circuit status is On.
Economizer is Off.
Bell icon is moving on controller’s
display.
String in the alarm list:
Cx EcoTempSen
String in the alarm log:
Cx EcoTempSen
String in the alarm snapshot
Cx EcoTempSen
Sensor is shorted.
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Sensor is broken.
Check if sensor is shorted with a
resistance measurement.
Sensor is not good connected (open).
Check for correct installation of the
sensor on refrigerant circuit pipe.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according with electrical scheme.