If the running current rises above the Running Current Hold limit (101% of RLA), compressor is inhibited to increase its
running capacity. This condition is indicated on the controller display in the circuit status as “Run: High VFD Amps”.
If the condensing pressure rises above the Running Current Unload limit (105% of RLA), compressor is unloaded in order
to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status as Run:
High VFD Amps”. The status is automatically cleared when the running amps falls below the hold limit.
4.2.5.5 High Discharge Temperature
When the compressor is running and its discharge temperature rises above the safety limits the circuit control logic reacts
at two different levels in order to recover the normal running conditions.
If the discharge temperature rises above the Discharge Temperature Hold limit (95 °C), compressor is inhibited to increase
its running capacity. This condition is indicated on the controller display in the circuit status as Run: High Discharge Temp”.
If the discharge temperature rises above the Discharge Temperature Unload limit (100 °C), compressor is unloaded in
order to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status
as “Run: High Discharge Temp”. The status is automatically cleared when the discharge temperature falls below the hold
limit.