D-EOMZC00204-18_04EN 14/54
When controlled temperature is within the dead band (DB) error from the active setpoint (AS), unit capacity will not be
changed.
If the leaving water temperature decreases below (Cool Mode) or rises above (Heat Mode) the active setpoint (AS), unit
capacity is adjusted to keep it stable. A further decreasing (Cool Mode) or increasing (Heat Mode) of the controlled
temperature of the Shut Down DT offset (SD) can cause circuit shutdown.
Thermostatic control settings are accessible from Main Page→ View/Set Unit → Thermostatic Control
Thermostat Control ON
Thermostat
Control OFF
Capacity load up
Capacity Unload
AS
AS+S
U
AS-SD
Thermostat Control OFF
Controlled
Temperature
DB
COOL MODE