3 About the box
Installer and user reference guide
7
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
For the installer
3 About the box
3.1 Overview: About the box
This chapter describes what you have to do after the box with the
outdoor unit is delivered on-site.
It contains information about:
Unpacking and handling the outdoor unit
Removing the accessories from the unit
Keep the following in mind:
At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
Prepare the path along which you want to bring the unit inside in
advance.
Lift the unit preferably with a crane and 2 belts of at least 8m long
as shown in the figure below. Always use protectors to prevent
belt damage and pay attention to the position of the unit's centre
of gravity.
e
d
a
c
c
b
a Packaging material
b Belt sling
c Protector
d Opening
e Forklift
NOTICE
Use a belt sling of ≤20mm wide that adequately bears the
weight of the unit.
A forklift can only be used for transport as long as the unit remains
on its pallet as shown above.
3.2 Outdoor unit
3.2.1 To unpack the outdoor unit
Remove the packaging material from the unit:
Take care not to damage the unit when removing the shrink foil
with a cutter.
Remove the 4 bolts fixing the unit to its pallet.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
3.2.2 To remove the accessories from the
outdoor unit
Make sure that all accessories are available in the unit.
a d ec
b
f g
h
i
1×/2×
a General safety precautions
b Installation manual and operation manual (panel 3)
c Remote controller (panel 3)
d Main switch handle (panel 1)
e Tie wraps (panel 3)
f Shut-off valves (panel 3)

Bekijk gratis de handleiding van Daikin EWYQ050CAWH, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWYQ050CAWH
CategorieNiet gecategoriseerd
TaalNederlands
Grootte8322 MB