Daikin EWYQ050CAWH handleiding
Handleiding
Je bekijkt pagina 30 van 56

10 Troubleshooting
Installer and user reference guide
30
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
9.2 Maintenance safety precautions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE:Risk of electrostatic discharge
Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.
WARNING
▪ Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply
panel, remove the fuses or open the protection devices
of the unit.
▪ Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
▪ Please note that some sections of the electric
component box are hot.
▪ Make sure you do not touch a conductive section.
▪ Do not rinse the unit. This may cause electric shocks or
fire.
9.3 Checklist for yearly maintenance
of the outdoor unit
Check the following at least once a year:
▪ Pressure relief valve hose (if present)
▪ Water pressure relief valve
▪ Electrical component box
▪ Water pressure
▪ Water filter
▪ Glycol concentration and pH-value
Pressure relief valve hose
Check whether the pressure relief valve hose is positioned
appropriately to drain the water.
Water pressure relief valve
Turn the red knob on the valve counter-clockwise and check if it
operates correctly:
▪ If you do not hear a clacking sound, contact your local dealer.
▪ In case the water keeps running out of the unit, close both the
water inlet and outlet shut-off valves first and then contact your
local dealer.
Switch box
Carry out a thorough visual inspection of the switchbox and look for
obvious defects such as loose connections or defective wiring.
WARNING
If the internal wiring is damaged, it has to be replaced by
the manufacturer, its service agent or similarly qualified
persons.
Water pressure
Check whether the water pressure is above 1bar. If it is lower, add
water.
Water filter
Clean the water filter.
NOTICE
Handle the water filter with care. Do NOT use excessive
force when you reinsert the water filter so as NOT to
damage the water filter mesh.
10 Troubleshooting
10.1 Overview: Troubleshooting
This chapter describes what you have to do in case of problems.
It contains information about:
▪ Solving problems based on error codes
10.2 Error codes: Overview
Main code Cause Solution
Failure writing memory (EEPROM error) Contact your local dealer.
Water circuit malfunction ▪ Check that water flow is possible (open all valves in the
circuit).
▪ Force clean water through the unit.
R410A expansion valve error (K11E/K12E) ▪ Check wiring connections.
▪ Contact your local dealer.
Water system warning ▪ Check filter.
▪ Make sure all valves are open.
▪ Contact your local dealer.
Capacity error Contact your local dealer.
Bad ACS communication Contact your local dealer.
R410A liquid thermistor error (R13T/R23T) ▪ Check wiring connections.
▪ Contact your local dealer.
Returning water thermistor error (R12T/R22T) ▪ Check wiring connections.
▪ Contact your local dealer.