7 Configuration
Installer and user reference guide
23
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
Setting
(= binary)
Value
Description
Power consumption limitation level via the external control adaptor
(DTA104A62)
If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied. The level is according to the table.
Level 1 Level 3<Level 2<Level 1
(default)
Level 2
Level 3
Enable the low noise function and/or power consumption limitation
via the external control adaptor (DTA104A62).
If the system needs to be running under low noise operation or
under power consumption limitation conditions when an external
signal is sent to the unit, this setting should be changed. This
setting will only be effective when the optional external control
adaptor (DTA104A62) is installed in the indoor unit.
(default)
Deactivated.
Activated.
7.2.9 Field settings on the remote controller
The user can change the field settings using the remote controller.
Each field setting is assigned a 3-digit number or code, e.g. [5-03],
which is indicated on the remote controller display. The first digit [5]
is the 'first code' or field setting group. The second and third digit [03]
together are the 'second code'.
See "7.2.9 Field settings on the remote controller" on page 23 for
an overview of all field settings and default values.
c
b
a
1 Press for a minimum of 5 seconds to enter the field setting
mode.
Result: (c), the current selected field setting code
(b) and the set value (a) are displayed.
2 Press to select the appropriate field setting first code.
3 Press to select the appropriate field setting second
code.
4 Press and to change the value of the selected
field setting.
5 Press to save the new value.
6 Repeat the previous steps to change other field settings as
required.
7 When finished, press to exit the field setting mode.
INFORMATION
▪ Changes made to a specific field setting are only stored
when is pressed. Navigating to a new field setting
code or pressing will discard any changes.
▪ Field settings are grouped by their first code, e.g. field
settings [0-00]; [0-01]; [0-02]; [0-03] are defined as
"Group 0". When different values are changed within
the same group, pressing will save all the values
changed within this group.
INFORMATION
▪ Before shipping, the set values have been set as
shown in "7.2.9 Field settings on the remote
controller"on page23.
▪ When exiting the field setting mode, " " may be
displayed on the remote controller LCD while the unit
initializes itself.
[0]Remote control setup
[0‑00] User permission level
The user permission level defines which buttons and functions are
available for the user. By default no level is defined, so all buttons
and functions are operable.
[0‑00] Description
2 Permission level 2
3 Permission level 3
Master Slave Permission level2 Permission level3
Operation ON/OFF
Setting the leaving water temperature —
Setting the room temperature
Quiet mode ON/OFF — —
Weather dependent setpoint operation ON/OFF —
Setting the clock — —
Programming the schedule timer — — —
Schedule timer operation ON/OFF —