8.2. Verify the appropriate installation location
8.2.1. General precautions on installation location
Select an installation site that meets the following requirements:
The foundation must be strong enough to support the weight of
the unit. The floor must be flat to prevent vibrations and noise
generation and to have sufficient stability.
The space around the unit is adequate for maintenance and
servicing (refer to "8.4. Installation space" on page 8).
The space around the unit allows sufficient air circulation.
There is no danger of fire due to leakage of inflammable gas.
The equipment is not intended for use in a potentially explosive
atmosphere.
Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone, and the location
is selected according the applicable legislation.
Take minimum and maximum water volumes and installation
heights into account, refer to "8.9. Water piping work" on page 9.
Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
Do not install in the following locations.
Locations where sulphurous acids and other
corrosive gases may be present in the
atmosphere.
Copper piping and soldered joints may
corrode, causing refrigerant to leak.
Locations where a mineral oil mist, spray or
vapour may be present in the atmosphere.
Plastic parts may deteriorate and fall off or
cause water leakage.
Locations where equipment that produces
electromagnetic waves is found.
The electromagnetic waves may cause the
control system to malfunction, preventing
normal operation.
Locations where flammable gases may leak,
where thinner, gasoline and other volatile
substances are handled, or where carbon
dust and other incendiary substances are
found in the atmosphere.
Leaked gas may accumulate around the unit,
causing an explosion.
Select a place where rain can be avoided as much as possible.
Be sure that the air inlet of the unit is not positioned towards the
main wind direction. Frontal wind will disturb the operation of the
unit. If necessary, use a screen to block the wind.
Ensure that water cannot cause any damage to the location by
adding water drains to the foundation and prevent water traps in
the construction.
Make sure the outdoor unit is NOT directly exposed to sea
winds. This is to prevent corrosion caused by high levels of salt
in the air, which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building
If the outdoor unit is exposed to direct sea winds, install a
windbreaker.
Mind the installation space requirements when installing the
windbreaker.
a Sea wind
b Building
c Outdoor unit
d Windbreaker
8.2.2. Selecting a location in cold climates
To prevent exposure to wind and snow, install a baffle plate on
the air side of the outdoor unit.
In heavy snowfall areas, it is very important to select an
installation site where the snow will not affect the unit (refer to
figure 1). If lateral snowfall is possible, make sure that the heat
exchanger coil is not affected by the snow (if necessary
construct a lateral canopy) and that the air blowing out of the unit
is not obstructed.
To prevent the unit from getting buried in snow, install it high
enough off the ground (if necessary construct a pedestal).
WARNING
Be sure to take adequate measures in order to prevent that
the unit is used as a shelter by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean and clear.
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit is suitable for installation in a commercial and
light industrial environment.
INFORMATION
When operating the unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.
b