All electrical equipment (not only the refrigerating system) shall be selected to be suitable for use in the zones
identified in the risk assessment. Electrical equipment shall be deemed to comply with the requirements if the
electrical supply is isolated when the refrigerant concentration reaches 25% of the lower flammable limit or less.
Machinery rooms or special machinery rooms shall be clearly marked as such on the entrances to the room,
together with warning notices indicating that unauthorized persons shall not enter and that smoking, naked light
or flames are prohibited. The notices shall also state that, in the event of an emergency, only authorized
persons conversant with emergency procedures shall decide whether to enter the machinery room. Additionally,
warning notices shall be displayed prohibiting unauthorized operation of the system
The owner / operator shall keep an updated logbook of the refrigerating system.