4.7.5 Hydraulic diagram
The unit is supplied with the following hydraulic components:
WATER CIRCUIT
Figure 12 Hydraulic diagram
N.B. The Pump kit is optional
WATER CIRCUIT EQUIPMENT
a.Pump
m.Expansion vessel
d.Drain
y.Water filter
e.Plugged fitting
TT Temperature sensor
f.Safety valve 3 BAR ½”
PI Pressure gauge
g.Shut off valve
FS Flowswitch
h.Air vent
If air, moisture or dust gets into the circuit problems may occur. To prevent this use shut-off valves, and water filter which
are delivered with the unit.
Legend:
a. Shut-off valve
b. Water filter
c. Threaded connector
Note: The hydraulic elements are supplied together with the unit and are located inside the cabinet.