D–EOMCP00104-14EN - 51/82
Controlled
Variable
Action
Set Point
Dead Band
Regulation Band
Max
0
-Max
Fig. 15 – Proportional action of VSD PID in cooling/iced mode
6.2.1.3.
VSD in heating mode
6.2.1.3.1. Control of evaporation temperature
When the system is operating in heating mode to control the evaporation temperature the
proportional gain is negative (the higher the input the lower the output).
Controlled
Variable
Action
Set Point
Dead Band
Regulation Band
Max
0
-Max
Fig. 16 – Proportional action of VSD PID in heating mode
6.2.1.3.2. Control of pressure ratio or temperature differences
When the system is operating in heating mode to control the pressure ration the proportional
gain is positive (the higher the input the higher the output).