6.4.2. OAT setpoint override
To enable the OAT setpoint override the unit limiting control expansion board pCO
e
#2 is
required, with the ambient sensor installed.
The base setpoint is modified on the base of outside ambient temperature and of a max reset
value, of a value of OAT to start reset and a value of OAT to apply max reset, as shown in fig 9
Fig. 9 – OAT setpoint override
6.4.3. Return setpoint override
The base setpoint is modified on the base of evaporator ∆T and of a max reset value, of a
value of OAT to start reset and a value of OAT to apply max reset, as shown in fig 10
Fig. 10 – Return setpoint override
Start Reset T
Base Setpoint
Max Reset
Reset Delta T
Evap ∆T
Used Setpoint
Start Reset T
Base Setpoint
Max Reset
Reset Delta T
OAT
Used Setpoint