6. MAIN CONTROLLER FEATURES
In the following the main features of the control software are described
6.1. Controller purpose
Then system will control the evaporator leaving water temperature to keep it at a setpoint
value.
The system operates to optimize components performances from the point of view of their
efficiency and of their duration.
The system assures a safe operation of the unit and of all components and prevents
dangerous situations.
6.2. Unit enabling
The control allows different ways to enable/disable the unit:
Keypad : Enter key on the keypad allows to switch between “Power OFF” mode and “Unit
On” if other signals allows this state
Local Switch: when the digital input “Unit On/Off” is open the unit is in Local switch
Off”; when the digital input “Unit On/Off” is closed the unit may be in “Unit On” or
“Remote switch Off” on the basis of the “Remote On/Off “ digital input
Remote Switch: when the local switch is On (“Unit On/Offdigital input closed) if the
digital input “Remote On/Off is closed the unit is in “Unit On”, when digital input
“Remote On/Off “ is open the unit is in “Remote switch Off”
Network : a BAS or a Monitoring system may send an On/Off signal trough the serial line
connection to put the unit on or in “Rem. Comm. Off”
Time schedule : a timetable allows to program “Time Schedule Off” on a week base; several
holiday days are include.
Ambient LockOut : the unit is not enabled to operate unless the ambient temperature is
higher than an adjustable value (default 15.0°C (59.0 F) )
To be in “Unit On” all the allowed signals must enable the unit.
6.3. Unit modes
The unit is able to work in the following modes:
Cooling:
When this mode is selected the control will operate to cool the evaporator water; the setpoint
range is +4.0 ÷ +14.0 °C, (39.2 ÷ 57.2 F) a freeze alarm setpoint is set to 2 °C (34.6 F)
(adjustable by the operator in the range +1 ÷ +3 °C (33.8 ÷ 37.4 F) ) and a freeze prevent
setpoint is set to 3 °C (37.4 F) (adjustable by the operator in the range: “freeze alarm setpoint
+ 1 ÷ +3 °C (“freeze alarm setpoint” + 1.8 F ÷ 37.4 F) ).