5. PHYSICAL INPUTS AND OUTPUTS
The following parameters are inputs and outputs of the electronic boards.
They are used internally and/or sent to pLAN and supervisory system according to software
requirements and to the monitoring requirements
5.1. ASDU01C controller #1 – Base unit and compressors #1 & #2 control
Analog Input Digital Input
Ch. Description Type
Ch.
Description
B1 Oil Pressure #1
4-20mA
DI1 On/Off Comp #1 (Cir. #1 Shut-off)
B2 Oil Pressure #2
4-20mA
DI2 On/Off Comp #2 (Cir. #2 Shut-off)
B3 Suction Pressure #1 (*)
4-20mA
DI3 Evaporator Flow Switch
B4 Discharge Temperature #1
PT1000
DI4 PVM or GPF Unit or #1 (**)
B5 Discharge Temperature #2
PT1000
DI5 Double setpoint
B6 Discharge Pressure #1
4-20mA
DI6 High Press. Switch #1
B7 Discharge Pressure #2
4-20mA
DI7 High Press. Switch #2
B8 Suction Pressure #2 (*)
4-20mA
DI8 Oil Level Switch #1 (**)
B9 Entering water Temp. Sensor
NTC
DI9 Oil Level Switch #2 (**)
B10 Leaving Water Temp. Sensor
NTC
DI10
Low Press. Switch #1
DI11
Low Press. Switch #2
DI12
Transition or Solid State Fault #1
DI13
Transition or Solid State Fault #2
DI14
Overload or Motor Protection #1
DI15
Overload or Motor Protection #2
DI16
Unit On/Off
DI17
Remote On/Off
DI18
PVM or GPF #2 (**)
Analog Output
Digital Output
Ch. Description Type
Ch. Description
AO1 Fan Speed control #1
0-10Vdc
DO1 Start Comp #1
AO2
Second Fan Speed control #1 or
Fan Modular
output #1
0-10Vdc
DO2 Load Comp #1
AO3 SPARE
DO3 Unload Comp #1
AO4 Fan Speed control #2
0-10Vdc
DO4 Liquid Injection #1
AO5
Second Fan Speed control #2
or Fan Modular
output #2
0-10Vdc
DO5 Liquid Line #1 (*)
AO6 SPARE DO6 1
st
Fan step #1
DO7 2
nd
Fan Step #1
DO8 3
rd
Fan Step #1
DO9 Start Comp #2
DO10
Load Comp #2
DO11
Unload Comp #2
DO12
Evaporator Water Pump
DO13
Unit Alarm
DO14
Liquid Injection #2
DO15
Liquid Line #2 (*)
DO16
1
st
Fan step #2
DO17
2
nd
Fan Step #2
DO18
3
rd
Fan Step #2
(*) In case EEXV driver is not installed. If EEXV driver is installed, low pressures should be detected through EEXV
driver.
(**) Optional