D–EOMCP00104-14EN - 24/82
Cooling/Glycol:
When this mode is selected the control will operate to cool the evaporator water; the setpoint
range are -8°C ÷ +14.0°C (17.6 ÷ 57.2 F) , a freeze alarm setpoint are set to –10 °C (14.0 F)
(adjustable by the operator in the range –12 °C ÷ -9°C (10.4 ÷ 15.8 F) ) and a freeze prevent
setpoint are set to –9 °C (15.8 F) (adjustable by the operator in the range “freeze alarm
setpoint” + 1°C ÷ -9 °C (“freeze alarm setpoint” + 1.8 F ÷ 15.8 F))
Ice:
When this mode is selected the control will operate to cool the evaporator water; the setpoint
range are -8°C ÷ +14.0°C (17.6 ÷ 57.2 F) , a freeze alarm setpoint are set to –10 °C (14.0 F)
(adjustable by the operator in the range –12 °C ÷ -9°C (10.4 ÷ 15.8 F) ) and a freeze prevent
setpoint are set to –9 °C (15.8 F) (adjustable by the operator in the range “freeze alarm
setpoint” + 1°C ÷ -9 °C (“freeze alarm setpoint” + 1.8 F ÷ 15.8 F))
While working in ice mode compressors are not be allowed to unload but are stopped using a
step procedure (se § 6.5.1)
Heating:
When this mode is selected the control will operate to heat the evaporator water; the setpoint
range is +30 ÷ +45°C (86 ÷ 113°C), a hot water alarm setpoint are set to 50°C (adjustable by
the operator in the range +46 ÷ +55°C (114.8 ÷ 131 F) ) and a hot prevent setpoint are set to
48°C (118.4 F) (adjustable by the operator in the range +46°C ÷ “hot water alarm setpoint” +
1°C (114.8 F ÷ “hot water alarm setpoint” + 1.8 F ) ).
Cooling + Heat Recovery:
Setpoints and freeze protection are managed as described in the cooling mode; in addition the
control will enable the heat recovery input and outputs foreseen on the expansion #2
Cooling/Glycol + Heat Recovery:
Setpoints and freeze protection are managed as described in the cooling/glycol mode; in
addition the control will enable the heat recovery input and outputs foreseen on the expansion
#2
Ice + Heat Recovery:
Setpoints and freeze protection are managed as described in the ice mode; in addition the
control will enable the heat recovery input and outputs foreseen on the expansion #2
The selection between cooling, cooling/glycol and ice mode are performed by the operator
using the interface under password.
The switching between cooling and ice and heating modes will cause the unit shutdown and
than the switching between the two modes.
6.4. Setpoints management
The control is able to manage the evaporator leaving water temperature on the base of
several inputs:
Changing the setpoint from the keypad