EWWP045~065KAW1M + ECB2+3MUAW
Packaged water-cooled water chillers
4PW61664-1
Operation manual
2
Technical specifications
(1)
Electrical specifications
(1)
(1) Refer to the engineering data book for the complete list of specifications.
General Hp 32 36 40 44 48 52 56 60 64 68 72
Nominal cooling
capacity
(a)
(kW)
86 99 112 121 130 142 155 168 177 186 195
Nominal input
(b)
(kW)
24.2 28.1 32.0 34.3 36.6 40.2 44.1 48.0 50.3 52.6 54.9
Dimensions HxWxD
(mm)
1200x600x1200 1800x600x1200
Machine weight
(kg)
600 620 640 654 668 920 940 960 974 988 1002
Connections
•water inlet (inch)
2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
•water outlet (inch)
2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
Compressor
Type hermetically sealed scroll
Qty x model
4x
JT212DA-YE
2x
JT212DA-YE +
2x JT300DA-YE
4x
JT300DA-YE
2x
JT300DA-YE +
2x JT335DA-YE
4x
JT335DA-YE
4x
JT212DA-YE
+ 2x
JT300DA-YE
2x
JT212DA-YE
+ 4x
JT300DA-YE
6x
JT300DA-YE
4x
JT300DA-YE
+ 2x
JT335DA-YE
2x
JT300DA-YE
+ 4x
JT335DA-YE
6x
JT335DA-YE
Speed
(rpm)
2900 2900
Oil type FVC 68D FVC 68D
Oil charge volume
(l)
4x 2.7 6x 2.7
Evaporator
Type brased plate heat exchanger
Qty 23
Nominal water flow
(l/min)
247 284 321 347 373 407 444 482 507 533 559
Water flow range
(l/min)
123 - 493 142 - 568 161 - 642 173 -694 186 - 745
204 - 814 222 - 889 241 -963 254-1015 267-1066 280-1118
Condenser
Type brased plate heat exchanger
Qty 23
Nominal water flow
(l/min)
314 362 410 442 474 519 567 614 647 679 711
Water flow range
(l/min)
157 - 629 181 -724 205 - 819 221 - 883 237 - 948
260-1038 283-1133 307-1229 323-1293 339-1357 355-1422
(a) The nominal cooling capacity is based on:
-entering water temperature of 12°C
-chilled water temperature of 7°C
-condenser in/out water temperature of 30/35°C
(b) The nominal input includes total input of the unit: compressor, control circuit and water pumps.
General Hp 32 36 40 44 48 52 56 60 64 68 72
Power supply
Phase
3N~ 3N~
•Frequency (Hz)
50 50
•Voltage (V)
400 400
•Voltage tolerance (%)
±10 ±10
Unit
Nominal running
current
(A)
41.6 47.0 52.4 56.2 60.0 67.8 73.2 78.6 82.4 86.2 90.0
Maximum running
current
(A)
56 64 72 76 80 92 100 108 112 116 120
Recommended fuses
according to IEC 269-2
(A)
3x 63 3x 63 3x 80 3x 80 3x 80 3x 100 3x 100 3x 125 3x 125 3x 125 3x 125
Compressor
Phase
3~ 3~
•Frequency (Hz)
50 50
•Voltage (V)
400 400
Nominal running
current
(A)
10.4 10.4/13.1 13.1 13.1/15 15
10.4/13.1 10.4/13.1
13.1 13.1/15 13.1/15 15

Bekijk gratis de handleiding van Daikin EWWP014KBW1N, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWWP014KBW1N
CategorieAirco
TaalNederlands
Grootte2818 MB