Packaged water-cooled water chillers
4PW61664-1
Operation manual
10
Safeties menu
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
Along with the basic information, more detailed information screens
can be consulted while the safety menu is active. Press the q key.
Screens similar to the following will appear.
History menu
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu. Warnings are also recorded.
Additionally the number of safeties that already occurred, can be
consulted on the first line of the history screens.
Info menu
Input/output menu
The "input/output" menu gives the status of all the digital inputs and
the relay outputs of the unit.
User password menu
Cooling/heating menu
To check the actual value of the
compressor timers (second screen).
To consult which unit safety caused
the shutdown.
To consult which module 1 safety
caused the shutdown.
To consult which module 2 safety
caused the shutdown.
To consult which module 3 safety
caused the shutdown.
To check the time and control mode
at the moment of the unit shutdown.
To check which were the common
evaporator and condenser inlet water
temperature.
To check which were the evaporator
outlet water temperature of all
modules at the moment of shutdown.
To check which was the status of the
compressors at the moment of
shutdown (first screen).
To check which was the status of the
compressors at the moment of
shutdown (second screen).
To check which were the total
amount of running hours of the com-
pressors at the moment of shutdown
(first screen).
To check which were the total
amount of running hours of the com-
pressors at the moment of shutdown
(second screen).
BW COMPRESSOR TIMERS
C22 GRD : 000s AR : 000s
C31 GRD : 000s AR : 000s
C32 GRD : 000s AR : 000s
BX UNIT SAFETY
0C9 : INL E SENSOR ERR
BX MODULE 1 SAFETY
1CA : OUT E SENSOR ERR
BX MODULE 2 SAFETY
2CA : OUT E SENSOR ERR
BX MODULE 3 SAFETY
3CA : OUT E SENSOR ERR
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
00h00 - 12/01/2001
MANUAL MODE
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
INL.E : 12.0°C STEP:
INL.C : 30.0°C 0
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
OUTE1 : 07.0°C OUTE3 :
OUTE2 : 07.0°C 07.0°C
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C11 : ON C21 :
C12 : ON ON
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C22 : ON
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH11 : 00000h RH21:
RH12 : 00000h 00000h
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH22 : 00000h
To consult time and date information.
To consult additional information
about the unit such as the unit type,
the refrigerant used and the manu-
facturing number.
To consult information about the con-
troller's software version.
To consult information about the
PCB.
To check whether any module
safeties are active.
To check the reverse phase protector
and if there's any waterflow to the
evaporator.
To check the status of the change-
able digital inputs.
To check the status of the compres-
sor relay outputs.
To check the status of the modules
low pressure bypass.
To check the status of the alarm
voltage free contact and the pump/
general operation contact.
To check the status of the change-
able relay output.
To change the user password.
To select cooling or heating mode.
BX TIME INFORMATION
TIME : 00h00
DATE : 00/01/2001
BC UNIT INFORMATION
UNITTYPE : WW-HP-32
MANUFACT. NR.: 0000000
REFRIGERANT : R134a
BC UNIT INFORMATION
SW : V1.0M6 (01/11/01)
SW CODE : FLDKNMCH0A
BW PCB INFORMATION
BOOT : V2.02-02/08/00
BIOS : V2.32-31/07/01
BX DIGITAL INPUTS
M1 SAFETY OK
M2 SAFETY OK
M3 SAFETY NOK
BC DIGITAL INPUTS
FLOWSWITCH : FLOW OK
REV.PHASE PR. : OK
BC CHANG. DIG. INPUTS
DI1 DUAL SETP : SETP.1
DI2 REM. ON/OFF : OFF
DI3 REM. C/H : COOL
BC RELAY OUTPUTS
C11 : ON C12 : ON
C21 : ON C22 : ON
C31 : ON C32 : OFF
BC RELAY OUTPUTS
LPBYPASS1 : CLOSED
LPBYPASS2 : CLOSED
LPBYPASS3 : OPEN
BC RELAY OUTPUTS
GEN. ALARM : CLOSED
PUMP/GEN OPER : CLOSED
BW CHANG. REL OUTPUTS
DO1 REV.VALVE(C/H) : O
B CHANGE PASSWORD
NEW PASSWORD : 0000
CONFIRM : 0000
B COOLING/HEATING
MODE : COOLING (EVAP)