D–EIMAC01905-23_06EN - 32/65
Any side of the unit must be accessible for post-installation maintenance operations. Fig. 24 shows the minimum space
required.
Vertical air discharge must not be obstructed for at least 5000mm.
In case of two chillers installed in free field, minimum recommended distance between them is 3600 mm; in case of two
chillers in a row, minimum distance is 1500 mm. The pictures below shows examples of recommended installations.
Should the unit be installed without observing the recommended minimum distances from walls and/or vertical obstacles,
there could be a combination of warm air recirculation and/or insufficient supply to the air-cooled condenser which could
cause a reduction of capacity and efficiency.
In any case, the microprocessor will allow the unit to adapt itself to new operating conditions and deliver the maximum
available capacity under any given circumstances, even if the lateral distance is lower than recommended, unless the
operating conditions should affect personnel safety or unit reliability.
d= 1800 mm for single circuit units; d= 3000/3500 mm (according to evaporator dimensions) for dual circuit units.
If h<Hc=2.4 m, minimum L=3.0 m; if h>Hc or L< 3.0 m
Contact your Daikin distributor to evaluate the various possible arrangements.
Fig. 24- Minimum clearance requirements