4.5 Network Control
When the unit controller is equipped with one or more communication modules the Network Control feature can be
enabled, which gives the possibility to control the unit via serial protocol (Modbus, BACNet or LON).
To allow unit’s control from network, follow below instructions:
1. Close the physical contact “Local/Network Switch”. Refer to unit electrical wiring diagram, Field Wiring
Connection page, to find the references about this contact.
2. Go to Main Page → View/Set Unit →Network Control
Set Controls Source = Network
Network Control menu returns all main values received from serial protocol.
Parameter
Range
Description
Control Source
Local
Network control disabled
Network
Network control enabled
Actual Control
Local,
Network
Active control between Local/BMS.
Enable
-
On/Off command from network
Mode
-
Operating mode from network
Cool LWT
-
Cooling water temperature setpoint from network
Heat LWT
-
Heating water temperature setpoint from network
Ice LWT
-
Ice water temperature setpoint from network
Current Limit
Setpoint for current limitation from BMS
Capacity Limit
-
Capacity limitation from network
Remote Server
Remote servers enable
Refer to communication protocol documentation for specific registers addresses and the related read/write access level.