D-EOMAC01905-23_01EN- 23/78
Parameter
Range
Description
Ext Alarm
Event
Event configuration generates an alarm in the controller but takes the unit
running
Rapid
Stop
Rapid Stop configuration generates an alarm in the controller and performs a
rapid stop of the unit
At the end of the
Setpoint Reset
configuration, execute an
Apply Changes
to make the
configurations made effective.
4.10 Power Conservation
In this chapters will be explained the functions used to reduce the unit power consumption:
1. Demand Limit
2. Current Limit
3. Setpoint Reset
4. Softload
Main Menu→View / Set Unit→Power Conservation
4.10.1 Demand Limit
The “Demand limit” function allows the unit to be limited to a specified maximum load. Capacity limit level is regulated
using an external 4-20 mA signal with a linear relationship shown in the picture below. A signal of 4 mA indicates the
maximum capacity available whereas a signal of 20 mA indicates the minimum capacity available. With demand limit
function is not possible shutdown the unit but only unload it until minimum admissible capacity. Demand limit related
setpoints available through this menu are listed in the table below.
To enable this option, go to Main Menu → Commission Unit → Configuration → Options and set the Demand
Limit parameter to Enable.
At the end of the
Setpoint Reset
configuration, execute an
Apply Changes
to make the
configurations made effective.
All info about this function is reported in the Main Menu → View/set Unit → Power Configuration → Demand
Limit page.