Thermostatic control settings are accessible from Main Page→Thermostatic Control
Parameter
Range
Description
Start Up DT
0-5°C
Delta temperature respect the active setpoint to start the unit
(startup of first compressor)
Shut Down DT
0-3°C
Delta temperature respect the active setpoint to stop the unit
(shutdown of latest compressor)
Stage Up DT
0-1.7°C
Delta temperature respect the active setpoint to start a compressor
Stage Down DT
0-3°C
Delta temperature respect the active setpoint to stop a compressor
Stage Up Delay
0-60 min
Minimum time between the compressors startup
Stage Down Delay
3-30 min
Minimum time between the compressors shutdown
Ice Cycle Delay
1-23 h
Unit standby period during Ice mode operation
Max Circuits Run
1-2
Limit to the number of circuits to be used
Next Circuit On
Shows next circuit to be started up
Next Circuit Off
Shows next circuit number to be stopped
4.7 Date/Time
The unit controller can take stored the actual date and time, that are used for:
1. Scheduler
2. Cycling of standby chiller with Master Slave configuration
3. Alarms Log
Date and time can be modified going in View/Set Unit → Date/Time
Thermostat Control ON
Thermostat
Control OFF
Capacity load up
Capacity Unload
AS
AS+S
U
AS-SD
Thermostat Control OFF
Controlled
Temperature
DB
COOL MODE