5.4.4 Gas Leakage Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Solution
Circuit status is On.
Bell icon is moving on controller’s
display.
String in the alarm list:
Cx GasLeakSen
String in the alarm log:
± Cx GasLeakSen
String in the alarm snapshot
Cx GasLeakSen
Sensor is broken.
Check for sensor integrity.
Check correct sensors operation
according to information about mVolt
(mV) range related to ppm values.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected
(open).
Check for correct installation of the
sensor.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according to electrical scheme.
Reset
Notes
Local HMI
Network
Auto
5.4.5 CxCmp1 MaintCode01
This alarm indicates that a component in the inverter may require verification or even a replacement.
Symptom
Cause
Solution
Circuit status is On.
The compressor keeps operating as
normal.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 MaintCode01
String in the alarm log:
± CxCmp1 MaintCode01
String in the alarm snapshot
CxCmp1 MaintCode01
The inverter cooling valve in the
inverter, may require a verification or
a replacement.
Contact your service organization to
get the problem solved.
Reset
Notes
Local HMI
Network
Auto
5.4.6 CxCmp1 MaintCode02
This alarm indicates that a component in the inverter may require verification or even a replacement.
Symptom
Cause
Solution
Circuit status is On.
The compressor keeps operating as
normal.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 MaintCode02
String in the alarm log:
± CxCmp1 MaintCode02
String in the alarm snapshot
CxCmp1 MaintCode02
The capacitors in the inverter, may
require a verification or a
replacement.
Contact your service organization to
get the problem solved.
Reset
Notes
Local HMI
Network
Auto