Daikin EWAH670TZXRB2 handleiding

78 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 34 van 78
D-EOMAC01905-23_01EN- 34/78
Parameter
Range
Description
Heater En
Off
The Option is not enabled.
On
The Option is correctly enabled
Delta Freeze
-5 +5°C
Difference between glycol entering or glycol leaving water temperature and glycol tank
freezing setpoint to enable the glycol tank heater.
In order Enable the Glycol Tank Heater functionality, the customer must set to On the “Heater En” parameter in the Glycol
Tank Heater page.
4.19 Harmonic Filter (SAF)
The Harmonic Filter (SAF) page can be accessed navigating through Main Menu View/Set Unit Harmonic
Filter.
The active harmonic filter is a power quality device that dynamically delivers a controlled current that has the same
amplitude as the harmonic current, which is injected in opposition to the harmonics present. This cancels the harmonic
currents in the electrical system.
Parameter
Range
Description
Filter On
Off
The Option is not enabled.
On
The Option is correctly enabled.
State
PwrOff
Power off (Waiting main supply)
WaitSSCmd
Waiting soft start command
SSCmdOn
Soft start command On
PreCOn
Capacitors pre charge On
PreCEnd
Capacitors pre charge End
WaitRun
Waiting Run
Run
SAF runs
SAFAlms
SAF generic Alarms
PCAlms
SAF Pre charge alarms
NoState
No state available

Bekijk gratis de handleiding van Daikin EWAH670TZXRB2, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWAH670TZXRB2
CategorieAirco
TaalNederlands
Grootte11657 MB