The unit can work with a primary or a secondary setpoint, that can be managed as indicated below:
1. Keypad selection + Double Setpoint digital contact
2. Keypad selection + Scheduler Configuration
3. Network
4. Setpoint Reset function
As first step the primary and secondary setpoints need to be defined. From main menu, with user password, press on
Setpoint.
Parameter
Range
Description
Cool LWT 1
Ranges of the Cool, Heat, Ice
setpoint are reported in the IOM of
every specific unit.
Primary cooling setpoint.
Cool LWT 2
Secondary cooling setpoint.
Ice LWT
Setpoint for Ice mode.
Max LWT
High limit for Cool LWT1 and Cool LWT2
Min LWT
Low limit for Cool LWT1 and Cool LWT2
HR EWT Sp
Heat Recovery Entering Water Setpoint
HR Dif
Heat Recovery Water Temperature differential
HR Lock Limit
Heat Recovery Lock Limit
HR Delta Sp
Heat Recovery Delta Setpoint
The change between primary and secondary setpoint can be performed using the Double setpoint contact, always
available in the user terminal box, or through the Scheduler function.
Double setpoint contact works as below:
- Contact opened, the primary setpoint is selected
- Contact closed, the secondary setpoint is selected
When the scheduler function is enabled, the Double setpoint contact is ignored
When the operating mode
Cool/Ice w/Glycol
is selected, the
Double Setpoint
contact will be
used to switch between the
Cool
and
Ice
mode, producing no change on the active setpoint