BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-
23_01EN_EWAD/H_EWFD/H -
T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 11 / 53
Software name:
ETRA / OMEGA
4.4 BACnet / IP software option
Option
enabling
1. From the HMI main menu choose:
2. Select “On” for option #3-BACNet IP
3. Insert the unlock password
4. Apply Changes
Option
configuration
5. From the HMI main menu choose:
6. Select “SW BACNet IP”
7. Select proper parameters for BACNet IP
communication
Parameter
Default value
Device Instance
1
UDP Port Number
47808 (BAC0)
DHCP
(1)
OFF
Given IP Address
2
127.0.0.1
Given IP Subnet Mask
2
255.255.255.000
Given Gateway
Address
2
127.0.0.1
Unit Support
English
NC Dev 1
0
NC Dev 2
0
(1) Verify whether DHCP should or should not be
enabled. If not, obtain the IP Subnet Mask of the
shared network from the network administrator.
Then, obtain static IP Addresses for all
MicroTech 4 Unit Controllers you are integrating
into the shared network. Finally, obtain the
address of an IP Router to use for sending IP
messages to and from the BACnet IP subnets.
(2) These addresses are used if DHCP (Dynamic Host Configuration Property) is set to Off. For
changes to these parameters to take effect, use the keypad/display and set Apply Changes
on the BACnet IP Setup menu to Yes. This will cause the power on the unit controller to
reset.
2
3
4
Commissioning→ Configuration→ Software Options
P
6
Commissioning