BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-
23_01EN_EWAD/H_EWFD/H -
T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 10 / 53
Software name:
ETRA / OMEGA
Configuration
parameters
Parameter
Default value
Notes
Device Instance
variable
The last 8 digits are computed from the production
number and date code.
MSTP Address
24 (0x18)
Cycle power after changing it for the changes to
take effect.
Baud Rate
38400
Baud rate
Number of devices
76800
64
38400
32
19200 and lower
Value not recommended
Max Master
127
Recommended value is the number of MS/TP
devices (device address) + 1
Max Info Frames
1
1, unless device generates high-priority events
(alarm, COV, client functionality).