BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 19 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Evaporator Pump 1 - Fault
BV
575
EvapPump1'Fault
0 NoAlarm
1 Alarm
R
Evaporator Pump 2 - Fault
BV
576
EvapPump2'Fault
0 NoAlarm
1 Alarm
R
Circ 1 Comp 1 Alarm - Low Pressure Ratio
BV
599
C1'Comp1'OFFPresRatioLow
0 NoAlarm
1 Alarm
R
Circ 2 Comp 1 Alarm - Low Pressure Ratio
BV
601
C2'Comp1'OFFPresRatioLow
0 NoAlarm
1 Alarm
R
Unit Alarm - Outside Air Temperature Sensor Fault
BV
605
Unit'OFFOATempSenFail
0 NoAlarm
1 Alarm
R
Circ 1 Comp 1 Alarm - High Motor Current
BV
606
C1'Comp1'OFFCurrentHi
0 NoAlarm
1 Alarm
R
Circ 2 Comp 1 Alarm - High Motor Current
BV
608
C2'Comp1'OFFCurrentHi
0 NoAlarm
1 Alarm
R
Circ 1 Comp 1 Alarm - High Motor Temperature
BV
637
C1'Comp1'OFFMotorTempHi
0 NoAlarm
1 Alarm
R
Circ 2 Comp 1 Alarm - High Motor Temperature
BV
639
C2'Comp1'OFFMotorTempHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Condenser Pressure Sensor Fault
BV
668
C1'OFFCondPresFail
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Condenser Pressure Sensor Fault
BV
670
C2'OFFCondPresFail
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Condenser High Pressure
BV
676
C1'OFFCondPresHi
0 NoAlarm
1 Alarm
R