BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 31 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
18946
74
Problem
Unit
NO EWT RESET - Entering Evaporator Temperature Sensor Failure
19202
75
Problem
Unit
INHIBIT LOAD - Evaporator Pressure Low
19490
76
Problem
Circuit 1
INHIBIT LOAD - Evaporator Pressure Low
19522
Problem
Circuit 2
19714
77
Problem
Unit
UNLOAD - Evaporator Pressure Low
20002
78
Problem
Circuit 1
UNLOAD - Evaporator Pressure Low
20034
Problem
Circuit 2
20262
79
Problem
C1.Comp1
UNLOAD - Compressor Motor Current High
20266
Problem
C1.Comp2
20294
Problem
C2.Comp1
20298
Problem
C2.Comp2
20513
80
Problem
Circuit 1
UNLOAD - Discharge Temperature High
20545
Problem
Circuit 2
20738
81
Problem
Pump 1
PUMP START ATTEMPTED - Evaporator Pump #1 Failure
20994
82
Problem
Pump 2
PUMP START ATTEMPTED - Evaporator Pump #2 Failure
21250
83
Problem
Unit
(Check Chiller Display for Cause)
21542
84
Problem
C1.Comp1
INHIBIT LOAD - Compressor Motor Current High
21546
Problem
C1.Comp2
21574
Problem
C2.Comp1
21578
Problem
C2.Comp2
21763
85
Problem
Unit
UNLOAD - Power Holes
22050
86
Problem
Circuit 1
INHIBIT FREECOOLING - Wrong Valve Position
22082
Problem
Circuit 2
22274
87
Problem
Unit
DATACENTER MODULE - SAF Side - Top Temperature Sensor Fault
22530
88
Problem
Unit
DATACENTER MODULE - SAF Side - Top Left Temperature Sensor Fault