BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 16 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circ 1 Compressor 1 - Suction Temperature
AI
105
C1'Comp1'SuctTemp
°C
R
Circ 1 Compressor 1 - Discharge Temperature
AI
63
C1'Comp1'DischTemp
°C
R
Circ 1 Compressor 1 - RLA Percentage
AV_RED
8
C1'Comp1'RLAPercent
%
R
Circ 1 Compressor 1 - Current
AI
9
C1'Comp1'Current
A
R
Circ 1 Compressor 1 - Power
AV_RED
45
C1'Comp1'Power
kW
R
Circ 1 Compressor 1 - Number of Starts
AV_RED
92
C1'Comp1'Starts
-
W
Circ 1 Compressor 1 - Number of Running Hours
AV_RED
74
C1'Comp1'RunHours
h
W
Circ 2 Compressor 1 - Suction Temperature
AI
108
C2'Comp1'SuctTemp
°C
R
Circ 2 Compressor 1 - Discharge Temperature
AI
66
C2'Comp1'DischTemp
°C
R
Circ 2 Compressor 1 - RLA Percentage
AV_RED
11
C2'Comp1'RLAPercent
%
R
Circ 2 Compressor 1 - Current
AI
12
C2'Comp1'Current
A
R
Circ 2 Compressor 1 - Power
AV_RED
48
C2'Comp1'Power
kW
R
Circ 2 Compressor 1 - Number of Starts
AV_RED
95
C2'Comp1'Starts
-
W
Circ 2 Compressor 1 - Number of Running Hours
AV_RED
77
C2'Comp1'Hours
h
W
Freecooling - Enable Setpoint
BV
28
Freecool'EnableStp
0 Disable
1 Enable
W
Freecooling - Status
MV_RED
31
Freecool'Status
1 Unit Off
2 FC Full
3 FC Mix
4 Mech
R
Freeccoling - Enabled State
MV_RED
32
Freecool'Enabled
1 No
2 Yes
R
AntiVacuum Protection State
BV
258
AntivacSta
0 No
1 Yes
R
Performance - Unit Thermal Capacity
AV_RED
260
ThermCapacity
kW
R