BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-
23_01EN_EWAD/H_EWFD/H -
T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 6 / 53
Software name:
ETRA / OMEGA
4. Commission this unit in a BACnet network
4.1 General information
Compatibility
The Microtech controllers are tested according to the BACnet Testing Laboratory (BTL)
Test Plan. They are designed to meet the requirements of the BACnet Standard as stated
in the Protocol Implementation and Conformance Statement (PICS). However, they are not
BTL listed. The PICS is located at the end of the present document.
Unit controller
Microtech 4 controller can be integrated in an interoperable BACnet network provided one
of the followings:
a) it is equipped with the proper communication module
b) the onboard communication has been made available (software option).
Communication
modules
Available communication modules to configure Microtech controllers in BACnet network
are:
1. BACnet/IP (dedicated network or shared Ethernet LAN)
2. BACnet MS/TP (Master/Slave Token Passing).
Both communication modules comply with the standardized profile for BACnet equipment
(B-AAC BACnet Advanced Application Controller).
BACnet/IP
(POL908)
BACnet MS/TP
(POL904)
Communication
software option
For Microtech 4, BACnet communication is also available 6nboard the controller as a
software option.
1. BACnet/IP (dedicated network or shared Ethernet LAN)
2. BACnet MS/TP (Master/Slave Token Passing).
Both communication options comply with the standardized profile for BACnet equipment
(B-AAC BACnet Advanced Application Controller).
BACnet/IP