BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-
23_01EN_EWAD/H_EWFD/H -
T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 12 / 53
Software name:
ETRA / OMEGA
4.5 BACnet MS/TP software option
Option
enabling
1. From the HMI main menu choose:
2. Select “On” for option #2-BACNet MSTP
3. Insert the unlock password
4. Apply Changes
Option
configuration
5. From the HMI main menu choose:
6. Select “SW BACNet MSTP”
7. Select proper parameters for BACNet MSTP
communication.
Parameter
Default
value
Notes
Device Instance
variable
-
Address
0
MSTP Address
Baud Rate
38400
Baud rate
Number of devices
76800
64
38400
32
19200 and lower
Value not recommended
Max Master
1
Recommended value is the number of MS/TP devices
(device address) + 1
Max Info
Frames
1
1, unless device generates high-priority events (alarm,
COV, client functionality).
2
3
4
Commissioning→ Configuration→ Software Options
Commissioning
6
P