BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 23 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circuit 1 Alarm - No Pressure change at Start
BV
905
C1'OFFNoPresChgAtStart
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - No Pressure change at Start
BV
906
C2'OFFNoPresChgAtStart
0 NoAlarm
1 Alarm
R
Circ 1 Compr 1 Alarm - VFD Fault
BV
762
C1'Comp1'OFFVfdFault
0 NoAlarm
1 Alarm
R
Circ 2 Compr 1 Alarm - VFD Fault
BV
888
C2'Comp1'OFFVfdFault
0 NoAlarm
1 Alarm
R
Circ 1 Compr 1 Alarm - VFD High Temperature
BV
942
C1'Comp1'OFFVfdTempHi
0 NoAlarm
1 Alarm
R
Circ 2 Compr 1 Alarm - VFD High Temperature
BV
944
C2'Comp1'OFFVfdTempHi
0 NoAlarm
1 Alarm
R
Circ 1 Compr 1 Alarm - VFD Communication Failure
BV
948
C1'Comp1'OFFVfdCommFail
0 NoAlarm
1 Alarm
R
Circ 2 Compr 1 Alarm - VFD Communication Failure
BV
950
C2'Comp1'OFFVfdCommFail
0 NoAlarm
1 Alarm
R
Unit Alarm - Emergency Stop Switch
BV
921
EmergencyStopAlarm
0 NoAlarm
1 Alarm
R
Unit Alarm - Evaporator Temperature Sensors Inverted
BV
922
EvapWTempInverted
0 NoAlarm
1 Alarm
R
Unit Alarm - External Alarm
BV
923
Unit'OFFExternalAlarm
0 NoAlarm
1 Alarm
R
Circ 1 Compr 1 Problem - Low Discharge Superheat
BV
961
C1'Comp1'DischSHeatLow
0 NoAlarm
1 Alarm
R