BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 21 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circuit 2 Alarm - Too many restart
BV
744
C2'OFFRestartsAlm
0 NoAlarm
1 Alarm
R
Unit Alarm - Evaporator Leaving Temperature Sensor Fault
BV
748
Unit'OFFEvapLvgWTempFail
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Mechanical High Pressure
BV
760
C1'OFFMechPressHi
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Mechanical High Pressure
BV
762
C2'OFFMechPressHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Oil Filter High Pressure
BV
796
C1'OFFOilFilterPresHi
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Oil Filter High Pressure
BV
798
C2'OFFOilFilterPresHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Oil Pressure Sensor Failure
BV
802
C1'OFFOilPresFail
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Oil Pressure Sensor Failure
BV
804
C2'OFFOilPresFail
0 NoAlarm
1 Alarm
R
Unit Alarm - Phase Voltage
BV
820
Unit'OFFPhaseVoltage
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - OverVoltage
BV
978
C1'OFFOverVoltage
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - OverVoltage
BV
982
C2'OFFOverVoltage
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - UnderVoltage
BV
979
C1'OFFUnderVoltage
0 NoAlarm
1 Alarm
R