BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 20 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circuit 2 Alarm - Condenser High Pressure
BV
678
C2'OFFCondPresHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Discharge Temperature Sensor Fault
BV
688
C1'OFFDischTempFail
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Discharge Temperature Sensor Fault
BV
690
C2'OFFDischTempFail
0 NoAlarm
1 Alarm
R
Circ 1 Comp 1 Alarm - High Discharge Temperature
BV
694
C1'Comp1'OFFDischTempHi
0 NoAlarm
1 Alarm
R
Circ 2 Comp 1 Alarm - High Discharge Temperature
BV
696
C2'Comp1'OFFDischTempHi
0 NoAlarm
1 Alarm
R
Unit Alarm - Evaporator Water Flow Loss
BV
701
Unit'OFFEvapFlowLoss
0 NoAlarm
1 Alarm
R
Unit Alarm - Evaporator Water Freeze
BV
702
Unit'OFFEvapLvgWTempLow
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Evaporator Pressure Low
BV
704
C1'OFFEvapPresLow
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Evaporator Pressure Low
BV
706
C2'OFFEvapPresLow
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Evaporator Pressure Sensor Failure
BV
711
C1'OFFEvapPresFail
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Evaporator Pressure Sensor Failure
BV
713
C2'OFFEvapPresFail
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Too many restart
BV
742
C1'OFFRestartsAlm
0 NoAlarm
1 Alarm
R