Daikin EWAD650TZSSD1 handleiding

53 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 53
BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 21 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circuit 2 Alarm - Too many restart
BV
744
C2'OFFRestartsAlm
0 NoAlarm
1 Alarm
R
Unit Alarm - Evaporator Leaving Temperature Sensor Fault
BV
748
Unit'OFFEvapLvgWTempFail
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Mechanical High Pressure
BV
760
C1'OFFMechPressHi
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Mechanical High Pressure
BV
762
C2'OFFMechPressHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Oil Filter High Pressure
BV
796
C1'OFFOilFilterPresHi
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Oil Filter High Pressure
BV
798
C2'OFFOilFilterPresHi
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Oil Pressure Sensor Failure
BV
802
C1'OFFOilPresFail
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Oil Pressure Sensor Failure
BV
804
C2'OFFOilPresFail
0 NoAlarm
1 Alarm
R
Unit Alarm - Phase Voltage
BV
820
Unit'OFFPhaseVoltage
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - OverVoltage
BV
978
C1'OFFOverVoltage
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - OverVoltage
BV
982
C2'OFFOverVoltage
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - UnderVoltage
BV
979
C1'OFFUnderVoltage
0 NoAlarm
1 Alarm
R

Bekijk gratis de handleiding van Daikin EWAD650TZSSD1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWAD650TZSSD1
CategorieAirco
TaalNederlands
Grootte5821 MB