Air cooled inverter water chiller
OPERATION
MANUAL
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
Operation Manual
45
Parameter
Default
Range
Max Reset (MR)
5.0°C
0.0°C 10.0°C
Max Reset OAT (MROAT)
15.5°C
10.0°C 29.4°C
Start Reset OAT(SROAT)
23.8°C
10.0°C 29.4°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)
Cool/Ice LWT
Setpoint Reset by External 4-20 mA Signal
The active setpoint is calculated applying a correction based on an external 4-20mA signal. 4 mA
corresponds to 0°C correction, while 20 mA corresponds to a correction of the active setpoint as
set in Max Reset (MR).
Parameter
Default
Range
Max Reset (MR)
5.0°C
0.0°C 10.0°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)
Cool/Ice LWT
Signal
4-20mA External signal
Setpoint Reset by Evaporator Return Temperature
The active setpoint is calculated applying a correction that depends on the evaporator entering
(return) water temperature. As evaporator ΔT becomes lower than the SRΔT value, an offset to
SROA
T
OAT
A
S
LWT SP
MR
LWT SP + MR
MROA
T
4mA
20mA
Signal
AS
LWT SP
MR
LWT SP + MR