Handleiding
Je bekijkt pagina 45 van 84

Air cooled inverter water chiller
OPERATION
MANUAL
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
Operation Manual
45
Parameter
Default
Range
Max Reset (MR)
5.0°C
0.0°C 10.0°C
Max Reset OAT (MROAT)
15.5°C
10.0°C 29.4°C
Start Reset OAT(SROAT)
23.8°C
10.0°C 29.4°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)
Cool/Ice LWT
Setpoint Reset by External 4-20 mA Signal
The active setpoint is calculated applying a correction based on an external 4-20mA signal. 4 mA
corresponds to 0°C correction, while 20 mA corresponds to a correction of the active setpoint as
set in Max Reset (MR).
Parameter
Default
Range
Max Reset (MR)
5.0°C
0.0°C 10.0°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)
Cool/Ice LWT
Signal
4-20mA External signal
Setpoint Reset by Evaporator Return Temperature
The active setpoint is calculated applying a correction that depends on the evaporator entering
(return) water temperature. As evaporator ΔT becomes lower than the SRΔT value, an offset to
SROA
T
OAT
A
S
LWT SP
MR
LWT SP + MR
MROA
T
4mA
20mA
Signal
AS
LWT SP
MR
LWT SP + MR
Bekijk gratis de handleiding van Daikin EWAD620TZPLB, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Daikin |
Model | EWAD620TZPLB |
Categorie | Airco |
Taal | Nederlands |
Grootte | 11976 MB |