OPERATION
MANUAL
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
Operation Manual
27
Sl1 EWT=
-
-
Display the Slave1 entering water temperature
Sl2 EWT=
-
-
Display the Slave2 entering water temperature
Sl3 EWT=
-
-
Display the Slave3 entering water temperature
Master Hrs=
-
-
Master running hours
Slave 1 Hrs=
-
-
Slave 1 running hours
Slave 2 Hrs=
-
-
Slave 2 running hours
Slave 3 Hrs=
-
-
Slave 3 running hours
Master Starts=
-
-
Master number of starts
Slave 1 Starts=
-
-
Slave 1 number of starts
Slave 2 Starts=
-
-
Slave 2 number of starts
Slave 3 Starts=
-
-
Slave 3 number of starts
4.2.5.2 Options
This menu allows to set main parameter of Master Slave funtion
Setpoint/Sub-
Menu
Default
Range
Description
Master Priority=
1
1…4
Start Up / Shut Down priority of the chiller Master
Priority = 1 highest priority
Priority = 4 lowest priority
Slave 1 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 1
Priority = 1 highest priority
Priority = 4 lowest priority
Slave 2 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 2.
Priority = 1 highest priority
Priority = 4 lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 3
Slave 3 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 3.
Priority = 1 highest priority
Priority = 4 lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 4
Master Enable=
Enable
Enable
Disable
This parameter allows to enable or disable locally the Master Chiller
Control Mode=
Complete
Partial
Complete
Parameter to select the Partial or Complete control mode
Partial On/Off control
Complete On/Off + Capacity control
Control Tmp=
Leaving
Entering
Leaving
Parameter to define the controlled temperature
Entering - Thermoregulations is based on the Average Entering Water Temperature
(AEWT)
Leaving - Thermoregulation is based on the Common Leaving Water Temperature
(CLWT)
4.2.5.3 Thermostat Ctrl
This page resumes all thermostat control parameter of Master Slave.
Setpoint/Sub-
Menu
Default
Range
Description
Stage Up DT=
2.7°C
0.5…5.0°C
Offset respect the active setpoint for the unit startup.
Stage Dn DT =
1.5°C
0.5…5.0°C
Offset respect the active setpoint for the unit shutdown.
Dead Band =
0.2
0.1 - Min(Stage UP DT, Stage Dn
DT)
Dead Band respect the active setpoint within which the load/unload
command are no longer generated
Threshold=
60%
30...100%
Threshold of load that have to reach all units running before start of
a new chiller
Stage Up Time=
5min
0min…20min
Minimum time between the start of two chillers
Stage Dn Time=
5min
0min…20min
Minim time between the stop of two chillers
Min Evap Tmp=
4.0
-18…30°C
Minimum Evaporator leaving water temperature
4.2.5.4 Timers
Setpoint/Sub-
Menu
Default
Range
Description
Stage Up Timer=
-
-
Current delay for new chiller stage up
Stage Dn Timer=
-
-
Current delay for new chiller stage down
Clear Timers=
Off
Off
Reset
This command, visible only with service password, can be used to reset the Stage Up/Dn
Timer.