BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 26 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circ 1 Compressor 1 - Operating State
BV
431
C1'Comp1'State
0 Stop
1 Run
R
Unit - Refrigerant type
MV_RED
1854
RefrigType
1 R22
2 R134a
3 R407c
4 R410a
5 R1234ze
5 resv3
R
Unit - Number of Circuits
AV_RED
1855
NrCircuits
1…2
R
Unit - Number of Compressors
AV_RED
1856
NrCompressors
1...4
R
Circuit 2 - Evaporator Superheat Active Setpoint
AV_RED
1896
C2'EvapSuperheatStpVal
dK
R
Circuit 1 - Evaporator Superheat Active Setpoint
AV_RED
1897
C1'EvapSuperheatStpVal
dK
R
Circuit 2 - Evaporator Superheat Temperature
AV_RED
1898
C2'EvapSuperheat
dK
R
Circuit 1 - Evaporator Superheat Temperature
AV_RED
1899
C1'EvapSuperheat
dK
R
Unit - Active Energy
AV_RED
990
ActEnergy
kWh
R
Unit - Power Factor
AV_RED
991
PowerFactor
-
R
Unit - Current Limit Setpoint
AV
995
NetworkCurrentLimitSetpoint
A
W
Variable Flow - Plant Differential Pressure
AI
1905
VarFlow'LoadDPres
kPa
W
Varibale Flow - Water Bypass Valve State
MV_RED
1906
VarFlow'WBypVlvSta
1 Closed
2 Opened
R
Varibale Flow - Plant Differential Pressure setpoint
AV_RED
1909
VarFlow'LoadDPresStpt
kPa
W
Variable Flow - Plant Delta Temperature
AV_RED
1911
VarFlow'DeltaTemp
°Dc
R
Variable Flow - Plant Delta Temperature Setpoint
AV_RED
1913
VarFlow'DeltaTempStp
°Dc
W
Variable Flow - Fixed Speed 1 Setpoint
AV_RED
1915
VarFlow'FixSpeedStp
%
W
Circuit 2 - Expansion Valve Position
AV_RED
208
C2'ExpValvePos
%
R
Circuit 2 - Fan Speed
AV_RED
209
C2'FanSpeed
%
R