Handleiding
Je bekijkt pagina 18 van 53

BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 18 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Unit - Model
MV_RED
317
UnitModel
1 Centrifugal
2 Water
Cooled
3 Air Cooled
4 HeatPump
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Other
R
Unit - Safety Mode Setpoint
MV_RED
318
SafetyModeSetpoint
0 Off
1 On
R
Unit - Safety Mode State
MV_RED
319
SafetyModeState
0 Off
1 On
R
Unit Alarm - Evaporator Entering Temperature Sensor Fault
BV
917
Unit'OFFEvapEntWTempFail
0 NoAlarm
1 Alarm
R
Unit Warning - Setpoint Reset Input Out of Range
BV
512
BadSetpointResetInput
0 NoAlarm
1 Alarm
R
Unit Warning - Demand Limit Input Out of Range
BV
513
BadDemandLimitInput
0 NoAlarm
1 Alarm
R
Circuit 1 Warning - Power Loss while Compressor Running
BV
529
C1'InhibitPwrLoss
0 NoAlarm
1 Alarm
R
Circuit 2 Warning - Power Loss while Compressor Running
BV
530
C2'InhibitPwrLoss
0 NoAlarm
1 Alarm
R
Unit Warning - Inhibition for Low Ambient Temperature
BV
533
Unit'InhibitOATLow
0 NoAlarm
1 Alarm
R