Daikin EWAD565TZXSD1 handleiding

53 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 43 van 53
BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 43 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
52555
Fault
C2.Comp2
52739
206
Fault
Unit
UNIT SHUTDOWN - Gas Leakage
52771
Fault
Circuit 1
CIRCUIT SHUTDOWN - Gas Leakage
52803
Fault
Circuit 2
52995
207
Fault
Unit
UNIT SHUTDOWN - Battery Mode
53251
208
Fault
Unit
UNIT SHUTDOWN - High Pitch (Marine)
53507
209
Fault
Unit
UNIT SHUTDOWN - High Roll (Marine)
53763
210
Fault
Unit
UNIT SHUTDOWN - Pitch Sensor Fault (Marine)
54019
211
Fault
Unit
UNIT SHUTDOWN - Roll Sensor Fault (Marine)
54275
212
Fault
Unit
UNIT SHUTDOWN - Evaporator Differenital Pressure Sensor Fault
54531
213
Fault
Unit
UNIT SHUTDOWN - Evaporator Differenital Pressure High
54787
214
Fault
Unit
UNIT SHUTDOWN - Condenser Differenital Pressure Sensor Fault
55043
215
Fault
Unit
UNIT SHUTDOWN - Condenser Differenital Pressure High
55335
216
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - VFD Card Temperature High
55339
Fault
C1.Comp2
55367
Fault
C2.Comp1
55371
Fault
C2.Comp2
55591
217
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - RLA High
55595
Fault
C1.Comp2
55623
Fault
C2.Comp1
55627
Fault
C2.Comp2
55847
218
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - RLA Low
55851
Fault
C1.Comp2
55879
Fault
C2.Comp1
55883
Fault
C2.Comp2

Bekijk gratis de handleiding van Daikin EWAD565TZXSD1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.