Daikin EWAD565TZXSD1 handleiding

53 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 41 van 53
BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 41 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
47915
Fault
C1.Comp2
47943
Fault
C2.Comp1
47947
Fault
C2.Comp2
47907
187
Fault
Circuit 1
CIRCUIT SHUTDOWN - Mechanical Low Pressure Trip #n
47939
Fault
Circuit 2
48131
188
Fault
Unit
Controller board offline #n
(Circuit number describe Control board number. 0=Unit alarm for Extension
modules other than Circuits extension)
48163
Fault
Circuit 1
48195
Fault
Circuit 2
48419
189
Fault
Circuit 1
CIRCUIT SHUTDOWN - No Pressure Change After Start
48451
Fault
Circuit 2
48675
190
Fault
Circuit 1
CIRCUIT SHUTDOWN - No Pressure at Startup
48707
Fault
Circuit 2
48935
191
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Slide position sensor Fault #n
48939
Fault
C1.Comp2
48967
Fault
C2.Comp1
48971
Fault
C2.Comp2
49155
192
Fault
Unit
UNIT STOP - Emergency Stop Alarm
49411
193
Fault
Unit
UNIT STOP - Evaporator Water Temperatures Inverted
49667
194
Fault
Unit
UNIT STOP - External Alarm
49923
195
Fault
Unit
UNIT SHUTDOWN - Evaporator Leaving Water Temperature 1 Sensor Fault
50179
196
Fault
Unit
UNIT SHUTDOWN - Evaporator Leaving Water Temperature 2 Sensor Fault
50435
197
Fault
Unit
UNIT SHUTDOWN - Evaporator 1 Freeze Protection
50691
198
Fault
Unit
UNIT SHUTDOWN - Evaporator 2 Freeze Protection
50983
199
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - VFD Fault #n
50987
Fault
C1.Comp2

Bekijk gratis de handleiding van Daikin EWAD565TZXSD1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWAD565TZXSD1
CategorieAirco
TaalNederlands