BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 34 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
34631
Fault
C2.Comp1
34635
Fault
C2.Comp2
34855
136
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - VFD Temperature Sensor Fault
34859
Fault
C1.Comp2
34887
Fault
C2.Comp1
34891
Fault
C2.Comp2
35111
137
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Phase Loss
35115
Fault
C1.Comp2
35143
Fault
C2.Comp1
35147
Fault
C2.Comp2
35367
138
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Phase Reversal
35371
Fault
C1.Comp2
35399
Fault
C2.Comp1
35403
Fault
C2.Comp2
35623
139
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - VFD Overvoltage
35627
Fault
C1.Comp2
35655
Fault
C2.Comp1
35659
Fault
C2.Comp2
35879
140
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - VFD Undervoltage
35883
Fault
C1.Comp2
35911
Fault
C2.Comp1
35915
Fault
C2.Comp2
36099
141
Fault
Unit
UNIT SHUTDOWN - Condenser Pressure Sensor Fault
36391
142
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault #n
36395
Fault
C1.Comp2