BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 24 / 53
Software name:
ETRA / OMEGA
Description
Type
Name
Instance
Range
Read/
Write
Circ 2 Compr 1 Problem - Low Discharge Superheat
BV
963
C2'Comp1'DischSHeatLow
0 NoAlarm
1 Alarm
R
Unit Warning - Curennt Limit Input Out Of Range
BV
918
BadCurrentLimitInput
0 NoAlarm
1 Alarm
R
Controller Alarm - Option Board Offline
BV
919
Unit'OFFOptBoardOffline
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Gas Leakage
BV
844
C1'OFFGasLeakage
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Gas Leakage
BV
845
C2'OFFGasLeakage
0 NoAlarm
1 Alarm
R
Unit - Electrical Panel Temperature
AI
187
SwitchBoxTemp
°C
R
Unit Warning - Electrical Panel Temp Sensor Fault
BV
983
Unit'SwitchBoxSensFault
0 NoAlarm
1 Alarm
R
Unit Warning - Electrical Panel High Temperature
BV
984
Unit'SwitchBoxTempHigh
0 NoAlarm
1 Alarm
R
Controller Alarm - Fan Board Offline
BV
837
Unit'OFFFanBoardOffline
0 NoAlarm
1 Alarm
R
Circuit 1 Alarm - Fan Fault
BV
838
C1'FanAlm
0 NoAlarm
1 Alarm
R
Circuit 2 Alarm - Fan Fault
BV
839
C2'FanAlm
0 NoAlarm
1 Alarm
R
Shunt Active Filter – Grid Voltage
AV_RED
951
SAFGridVoltage
V
R
Shunt Active Filter – Grid Active Power
AV_RED
952
SAFGridActivePower
kW
R