Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
UnitOffEvapWaterFlow 
String in the alarm log: 
 UnitOffEvapWaterFlow 
String in the alarm snapshot 
UnitOffEvapWaterFlow 
Check the flow switch calibration and 
adapt to minimum water flow. 
Check    if  pump  impeller  can  rotate 
freely and has no damages. 
Check  pumps  protection  devices 
(circuit  breakers,  fuses,  inverters, 
etc.) 
Check flow switch connections. 
6.1.4.8  Evaporator Water Freeze Protect alarm 
This alarm is generated to indicate that the water temperature (entering or  leaving) has dropped 
below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the 
water circulate.  
Symptom 
Cause 
Solution 
Unit status is Off. 
All circuits are stopped immediately. 
Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
UnitOffEvapWaterTmpLo 
String in the alarm log: 
 UnitOffEvapWaterTmpLo 
String in the alarm snapshot 
UnitOffEvapWaterTmpLo 
Water flow too low. 
Increase the water flow. 
Inlet temperature to the evaporator is 
too low. 
Increase the inlet water temperature. 
Flow switch is not working or no water 
flow. 
Check  the  flow  switch  and  the  water 
pump. 
Refrigerant  temperature  become  too 
low (< -0.6°C). 
Check  the  water  flow  and  filter.  No 
good heat exchange condition into the 
evaporator. 
Sensors  readings  (entering  or 
leaving) are not properly calibrated 
Check  the  water temperatures  with  a 
proper  instrument  and  adjust  the 
offsets 
6.1.4.9  Heat Recovery Water Freeze Protect alarm 
This alarm is generated to indicate that the heat recovery water temperature (entering or leaving) 
has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and 
letting the water circulate.  
Symptom 
Cause 
Solution 
Unit status is Off. 
All circuits are stopped immediately. 
Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
UnitOff HRFreeze 
String in the alarm log: 
 UnitOff HRFreeze 
String in the alarm snapshot 
UnitOff HRFreeze 
Water flow too low. 
Increase the water flow. 
Inlet temperature to the heat recovery 
is too low. 
Increase the inlet water temperature. 
Sensors  readings  (entering  or 
leaving) are not properly calibrated 
Check  the  water temperatures  with  a 
proper  instrument  and  adjust  the 
offsets 
6.1.4.10 External alarm 
This alarm is generated to indicate that an external device whose operation is linked with this unit 
operation. This external device could be a pump or an inverter. 
Symptom 
Cause 
Solution 