Air cooled inverter water chiller
OPERATION
MANUAL
Operation Manual
30
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
4.2.11 Controller IP setup
The Microtech ® III controller has an embedded web server showing a replica of the onboard HMI
screens. To access to this additional web HMI can be required to adjust the IP settings to match
the settings of the local network. This can be done in this page. Please contact your IT department
for further information on how to set the following setpoints.
To activate the new settings a reboot of the controller is required, this can be done with the Apply
Changes setpoint.
The controller also supports DHCP, in this case the name of the controller must be used.
Setpoint/Sub-Menu
Default
Range
Description
Apply Changes=
No
No, Yes
DHCP=
Off
Off, On
Act IP=
Active IP address
Act Msk=
Active Subnet mask
Act Gwy=
Active Gateway
Gvn IP=
Given IP address (it will become the active)
Gvn Msk=
Given Subnet mask
Gvn Gwy=
Given Gateway
PrimDNS
Primary DNS
SecDNS
Secondary DNS
Name
Controller Name
MAC
Controller MAC Address
Check with IT Department on how to set these properties in order to connect the Microtech III to
the local network.
4.2.12 Daikin on Site
This menu allows to the user to enable the communication with Daikin cloud DoS (Daikin on Site) .
This option requires that the controller has access to internet. Please contact your service
organization for more details.
Setpoint/Sub-Menu
Default
Range
Description
Comm Start=
Off
Off, Start
Command to enable the communication
Comm State=
-
-
IPErr
Init
InitReg
Reg
RegErr
Descr
Connected
Communication state.
The communication is established only if this parameter displays Connected
Cntrlr ID=
-
-
Controller ID. This parameter is helpful to identify the specific controller in DoS
Activation Key=
-
-
Activation Key
4.2.13 Menu Password
It is possible to keep the User level always active to avoid to enter the User password. To do this
the Password Disable setpoint shall be set to On.
Pwd Disable=
Off
Off, On
4.3 View/Set Circuit
In this section it is possible to select between the available circuits and access data available for
the circuit selected.
Setpoint/Sub-Menu
Default
Range
Description